Pennsylvania HB 2535: An Act providing for the testing and labeling of baby food and for prohibited levels of toxic heavy metals in baby food; and imposing duties on the Department of Health.
Status: PN 3012 Referred to HEALTH (as of 2022-04-22)
State: Pennsylvania · Session: 2021-2022 · Bill: HB 2535
Sponsors: Hanbidge, Ciresi, Daley, Delloso, Hill-Evans, Hohenstein, Howard, Innamorato, Kinsey, Madden, Mcneill, O'Mara, Rabb, Samuelson, Sanchez, Sims
Bill Text
PRINTER'S NO. 3435 THE GENERAL ASSEMBLY OF PENNSYLVANIA HOUSE BILL No. 2535 Session of 2026 INTRODUCED BY SAPPEY, WAXMAN, PROKOPIAK, HILL-EVANS, PROBST, WEBSTER, MAYES, BOROWSKI, SHUSTERMAN, SANCHEZ, DONAHUE, CEPEDA-FREYTIZ, BOYD, STEELE, SCOTT AND MADSEN, MAY 26, 2026 REFERRED TO COMMITTEE ON VETERANS AFFAIRS AND EMERGENCY PREPAREDNESS, MAY 27, 2026 AN ACT Providing for the public safety regulation of large load users; requiring the submission of emergency operations plans and generalized infrastructure inventories as a condition of occupancy; protecting confidential security information; and providing for enforcement and penalties. The General Assembly of the Commonwealth of Pennsylvania hereby enacts as follows: Section 1. Short title. This act shall be known and may be cited as the Commercial Data Center Public Safety Act. Section 2. Definitions. The following words and phrases when used in this act shall have the meanings given to them in this section unless the context clearly indicates otherwise: "Building code official." A construction code official certified in accordance with the act of November 10, 1999 (P.L.491, No.45), known as the Pennsylvania Construction Code Act, to administer and enforce the Uniform Construction Code. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 "Emergency operations floor plan." A schematic document indicating the spatial layout of a large load user that identifies the: (1) Location of all emergency power shutoff switches. (2) Aisle containment systems and egress paths. (3) Battery storage rooms, including battery chemistry types. (4) Fire suppression system zones and manual activation points. (5) Locations of bulk storage for cooling agents, refrigerants or diesel fuel. "Generalized infrastructure inventory." A nonproprietary summary of the physical assets within the facility that pose potential thermal or chemical hazards, including: (1) The aggregate quantity and chemistry of uninterruptible power supply battery systems. (2) The type and volume of cooling agents or refrigerants used in thermal management systems. (3) The approximate density of server racks per square foot. (4) The presence of any immersion cooling systems involving dielectric fluids. "Large load user." A facility, campus of facilities or array of interconnected facilities in this Commonwealth that meets all of the following criteria: (1) Is used by a business entity or other enterprise to operate, manage or maintain a computer, group of computers or other organized assembly of hardware and software for the primary purpose of processing, storing, retrieving or transmitting data. 20260HB2535PN3435 - 2 - 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 (2) Has a peak demand of 25 megawatts or greater. "Local fire official." All of the following that have primary jurisdiction over the municipality in which the large load user is located: (1) The county emergency management coordinator. (2) The local emergency management coordinator. (3) The fire chief or designated officer in charge of the fire department or volunteer fire company. Section 3. Conditions for certificate of occupancy. (a) Requirement.--A building code official may not issue a certificate of occupancy for a large load user unless the applicant has demonstrated compliance with the reporting requirements of this section and with the act of November 10, 1999 (P.L.491, No.45), known as the Pennsylvania Construction Code Act. (b) Submission to local fire official.--Prior to the issuance of a certificate of occupancy, the owner or operator of a large load user shall submit the following to the local fire official with jurisdiction over the facility: (1) The emergency operations floor plan. (2) The generalized infrastructure inventory. (c) Proof of compliance.--The applicant shall provide the building code official with written proof that the documents required under subsection (b) have been received by the local fire official. Proof of compliance may include: (1) a signed receipt or written acknowledgment from the local fire official; or (2) proof of delivery via certified mail or a confirmed electronic transmission to the official address of the fire department. 20260HB2535PN3435 - 3 - 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Section 4. Annual updates and material changes. (a) Annual verification.--On or before March 1 of each year following the issuance of the certificate of occupancy, the operator of a large load user shall submit an updated generalized infrastructure inventory to the local fire official or a written statement certifying that no material changes have occurred since the previous submission. (b) Material changes.--In the event of a significant modification to the facility, including an increase in power load exceeding 20% or a change in the type of battery chemistry or cooling agents used, the operator shall submit an updated emergency operations floor plan
View Pennsylvania HB 2535 on LegisTrack → — full text, sponsors, votes, campaign finance, and cross-state matches.